GETTING STARTED MANUAL REVISION 2.0
11
All setpoints should be displayed on the MCS-Magnum and reviewed for correctness. Specific attention
should be paid to the following Setpoints:
Verify / set ‘Full Load Amps’
Verify / set ‘Target’ (supply air / leaving liquid)
‘Low Suction, Freeze’.
‘High Disc’ based on water or air-cooled
‘Condenser‘ setpoints
You are now ready to turn on main power.
Once main power is ON verify the following:
All Relay Outputs are in ‘AUTO’. (Not ’Lockout’)
Flow switch is ‘ON’ or ‘YES’.
RUN/STOP is in ‘RUN’.
Assuming additional capacity is required the control state should go to ‘LOADING’. Once the delay
has reached zero the lead compressor will turn on. (If a screw with oil, then the oil pump will come
on first)
When the compressor comes on the LLS should open. (There may be a pre-pump out to eliminate
liquid from reaching the compressor for direct expansion systems.)
Watch suction, discharge, amps etc. to verify the unit is running normally.
For screw compressors: Verify if the load and unload pulse timing setpoints need adjusting. The
pulse should allow the slide to move so the amps are moving but not overshooting the target. You
may need to also adjust the amp deadband setpoints if the system seems to hunt. (Amp deadband
should be about 3-4% of FLA)
Fine-tuning should now be done. (ROC, step delay, control zone, etc.)